Electronic Current Burden (1A)
Electronic Current Burden M400 is designed to provide a programmable burden in the secondary circuits of current transformers during verification, calibration, and testing. The device is intended for use with current transformers having a nominal secondary current of 1 A
FEATURES AND BENEFITS
- Wide range of burden values according to standards: IEC 61869-2, IEC 60044-1, IEEE C57.13
- Rated current – 1 A
- Rated power range: 0,5 to 50 VA, cos φ = 0,8 at 50 Hz 0; 0,5 to 50 VA, cos φ = 1 at 50 Hz
- Input cable, contact and internal test set resistances are compensated by four-conductor connection
- Non-breaking measuring circuit during switching of the burden
- Possibility of using with automated current transformer calibration systems
- Small size and low weight
VERSIONS
Electronic Current Burden М400 is available in two versions:
- М400.1 allows current transformer calibration in secondary current range 1…120 % of rated current
- М400.2 allows current transformer calibration in secondary current range 1…150 % of rated current
APPLICATIONS
Electronic Current Burden M400 is used by:
- Manufacturers of Current Transformers
- On-site testing of Current Transformers
- Calibration laboratories
- Metrology institutes
|
Specification |
Value |
|
|
Rated current |
1 A |
M400.1 / M400.2 |
| Current range |
1…120 % |
M400.1 |
| 1…150 % |
M400.2 |
|
| Rated burden power for cos φ = 0,8 | 0,5; 0,75; 1; 1,25; 1,5; 1,75; 1,875; 2; 2,5; 3; 3,75; 4; 5; 6,25; 7,5; 10; 11,25; 12,5; 15; 20; 25; 30; 40; 45*; 50* VA |
M400.1 / M400.2 |
| Rated burden power for cos φ = 1 | 0; 0,5; 0,75; 0,8; 1; 1,25; 1,5; 1,875; 2; 2,5; 3,75; 4; 5; 6; 7,5; 10; 12,5; 15; 30; 50* VA |
M400.1 / M400.2 |
| Active and reactive power error |
± 0,03·S** for 0,8 < S < 50 VA |
M400.1 / M400.2 |
|
± 0,04·S for S = 0,75 VA |
||
|
± 0,06·S for S = 0,5 VA |
||
|
± 0,05 VA for S = 0 VA |
||
* Burden power values are possible for 1 to 120 % of rated current.
** Setted burden power value.
| Power mains | |
|
Rated voltage Rated freguency |
220/230 V 50 Hz |
| Operating temperature | 0…40 °С |
| Relative humidity | up to 80 % non-condensing |
| Size (W × H × D) | 250 × 140 × 330 mm |
| Weight (Main unit) | 5 kg |
| Standards
Safety EMC |
EN 61010-1:2010 EN 61326-1:2013 |