M410

Electronic Voltage Burden

Electronic Voltage Burden M410 is a programmable device used as a burden in the secondary circuits of voltage transformers during their verification and calibration

FEATURES AND BENEFITS

  • Wide range of burden power values for voltage transformers in accordance with standards: IEC 60044, IEC 61869
  • Rated secondary voltages 100/3, 100/√3, 100, 110/3, 110/√3, 110 V
  • Rated power range:

1 to 10 VA, cos φ = 1 at 50 Hz

5 to 600 VA, cos φ = 0,8 at 50 Hz

  • Sets 100 % and 25 % rated power
  • Compatible for integration into a computer-controlled test system combined with Voltage Transformer Test Set M210/M211
  • Voltage overload protection
  • Wide range of emulated burden ratios
  • Small size and low weight

 

VERSIONS

Electronic Voltage Burden М410 is available in two versions:

  • M410.1 sets a burden in a range 20…120 % of rated voltage
  • M410.2 sets a burden:

over 120 VA in a range 20…120 % of rated voltage

1 to 100 VA in a range 20…200 % of rated voltage

 

 

APPLICATIONS

Electronic Voltage Burden M410 is used by:

  • Manufacturers of Current Transformers
  • On-site testing of Current Transformers
  • Calibration laboratories
  • Metrology institutes
Rated voltage, V

cos φ

Rated power, VA
М410.1

М410.2

100, 100/√3

0,8

10; 15; 25; 30; 50; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

5, 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

100, 100/√3

1,0

1, 2; 2,5; 3; 4, 5, 6, 7, 8, 9, 10

100/√3

0,8

10; 15; 25; 30; 50; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

5, 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

100/√3

1,0

1, 2; 2,5; 3; 4, 5, 6, 7, 8, 9, 10

100/3, 110/3

0,8

10; 15; 20, 25; 30; 50; 75; 100; 120; 150; 200

5; 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200

100/3, 110/3

1,0

1, 2; 2.5; 3; 4, 5, 6, 7, 8, 9, 10

110, 110/√3

0,8

5, 10; 15; 20; 25; 30; 50; 60; 75; 100; 120; 150; 200; 300; 360; 400; 500; 600

110, 110/√3 1,0

1, 2; 2,5; 3; 4, 5, 6, 7, 8, 9, 10

Sets 100 % and 25 % rated burden power

 

Active and reactive power errors ± 0,03·S*

Power mains

Rated voltage

Rated frequency

 

220/230 V

50 Hz

Operating temperature 0…40 °C
Relative humidity up to 80 % non-condensing
Size (W × H × D) 250 × 140 × 335 mm
Weight 9,5 kg

Standards

Safety

EMC

 

EN 61010-1:2010

EN 61326-1:2013

* Setted burden power value.

** The manufacturer reserves the right to change the characteristics of the device.