D100

Insulation Diagnostic System

Insulation Diagnostic System D100 measures the capacitance and dissipation/power factor, excitation current, transformer turns ratio with the test voltage up to 12 kV
For a more detailed analysis the device makes it possible to obtain the dependence dissipation/power factor on frequency (frequency sweep) and voltage (tip-up)

FEATURES AND BENEFITS

  • Dissipation/power factor and capacitance testing
  • Test voltage up to 12 kV
  • Output Power – 2400 V·A
  • Frequency 15…400 Hz
  • High accuracy of field measurements with high-interference environments
  • Temperature correction of dissipation/power factor
  • Fast measurements with adaptive filtering of the interference currents
  • Safe operation with safety switch, emergency stop, grounding control
  • Small size and low weight

APPLICATIONS

Dissipation/power factor and capacitance testing of:

  • Power transformers
  • Reactors
  • Instrument transformers
  • Bushings
  • Switches
  • Surge arresters
  • Capacitors
  • Cable
Name Range Resolution Accuracy
Dissipation Factor 0…10000% 0,001% ± (0,5 % rdg + 0,01 %)
Power Factor 0…100% 0,001% ± (0,5 % rdg + 0,01 %)
Capacitance 5 pF…6 μF 0,01 pF ± (0,1 % rdg + 0,1 pF)
Inductance 2 H…2 MH 0,1 mH ± (0,5 % rdg + 1 mH)
Test voltage 100…12000 V 1 V ± (0,3 % rdg + 1 V)
Current 20 μA …200 mA 0,1 μA ± (0,3 % rdg + 1 μA)
 Real power 0…400 W 0,1 mW ± (0,8 % rdg + 1 mW)
Frequency 15…400 Hz 0,01 Hz ± (0,1 % rdg + 0,1 Hz)

* Tolerances are determined for 45…70 Hz frequency range of the test voltage

Output
Power 2400 V·A
Voltage 100…12000 V (45…70 Hz)

100…4000 V (15…400 Hz)

Current <100 mA (continuously)

<200 mA (2 min ON, 8 min OFF)

 

Power mains
Rated voltage 110…240 V
Rated frequency 50/60 Hz
Operating temperature -20…50 °C
Relative humidity up to 95 % non-condensing
Size (Main Unit) 546 × 347 × 247 mm
Weight (Main Unit) 27 kg

 

Standards
Safety EN 61010-1:2010
EMC EN 61326-1:2013

 

Calibration Interval 2 years recommended